INPUTS/OUTPUTS
There are 96 virtual outputs that can be assigned using FlexLogic. If not assigned, the output is forced to 'OFF' (Logic 0). An
ID also can be assigned to each virtual output. Virtual outputs are resolved in each pass through the evaluation of the
FlexLogic equations. Any change of state of a virtual output can be logged as an event if programmed to do so.
For example, if Virtual Output 1 is the trip signal from FlexLogic and the trip relay is used to signal events, the settings is
programmed as follows:
VIRTUAL OUTPUT 1 ID
VIRTUAL OUTPUT 1 EVENTS

5.9.5 Resetting

SETTINGS  INPUTS/OUTPUTS  RESETTING
 RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism holds all of the latched indicators or messages in the set state after the initiating condition
has cleared until a
The
command can be sent from the faceplate
RESET
programmed operand.
When the
command is received by the relay, two FlexLogic operands are created. These operands, which are stored
RESET
as events, reset the latches if the initiating condition has cleared. The three sources of
FlexLogic operand. Each individual source of a
RESET OP
,
(PUSHBUTTON)
RESET OP (COMMS)
selects the operand that creates the
5

5.9.6 Direct inputs and outputs

5.9.6.1 Direct inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT INPUTS  DIRECT INPUT 1(32)
 DIRECT INPUT 1
These settings specify how the direct input information is processed.
DIRECT INPUT 1 NAME
DIRECT INPUT 1 DEVICE ID
identified here.
DIRECT INPUT 1 BIT NUMBER
identified as
DIRECT INPUT 1 BIT NUMBER
DIRECT INPUT 1 DEFAULT STATE
following choices are available:
On — Defaults the input to Logic 1
Off — Defaults the input to Logic 0
5-266
: "Trip"
: "Disabled"
RESET OPERAND:
Off
command is received to return these latches (not including FlexLogic latches) to the reset state.
RESET
or
to identify the source of the command. The
RESET OP (OPERAND)
RESET OP (OPERAND)
DIRECT INPUT 1
NAME: Dir Ip 1
DIRECT INPUT 1
DEVICE ID: 1
DIRECT INPUT 1
BIT NUMBER: 1
DIRECT INPUT 1
DEFAULT STATE: Off
DIRECT INPUT 1
EVENTS: Disabled
— This setting allows the user to assign a descriptive name to the direct input.
— Represents the source of direct input 1. The specified direct input is driven by the device
— The bit number to extract the state for direct input 1. Direct Input 1 is driven by the bit
. This corresponds to the direct output number of the sending device.
— Represents the state of the direct input when the associated direct device is offline. The
Range: FlexLogic operand
button, a remote device via a communications channel, or any
RESET
command also creates its individual operand
RESET
operand.
Range: up to 12 alphanumeric characters
Range: 1 to 16
Range: 1 to 32
Range: On, Off, Latest/On, Latest/Off
Range: Enabled, Disabled
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
commands each create the
RESET
RESET OP
setting here
RESET OPERAND