5.7.9 Breaker failure

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  BREAKER FAILURE  BREAKER FAILURE 1(2)
 BREAKER FAILURE 1
5
5-214
Figure 5-114: Ground IOC1 logic
SETTING
GROUND IOC1
PICKUP:
AND
RUN
IG
PICKUP
BF1 FUNCTION:
Disabled
BF1 MODE:
3-Pole
BF1 SOURCE:
SRC 1
BF1 USE AMP SUPV:
Yes
BF1 USE SEAL-IN:
Yes
BF1 3-POLE INITIATE:
Off
BF1 BLOCK:
Off
BF1 PH AMP SUPV
PICKUP: 1.050 pu
BF1 N AMP SUPV
PICKUP: 1.050 pu
BF1 USE TIMER 1:
Yes
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 2:
Yes
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 3:
Yes
BF1 TIMER 3 PICKUP
DELAY: 0.000 s
BF1 BKR POS1
A/3P:
Off
FLEXLOGIC OPERANDS
GROUND IOC1 PKP
GROUND IOIC DPO
SETTINGS
GROUND IOC1 OP
GROUND IOC1 PICKUP
DELAY:
GROUND IOC1 RESET
DELAY:
t
PKP
t
RST
Range: Disabled, Enabled
Range: 3-Pole, 1-Pole
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Yes, No
Range: Yes, No
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
827037A5.VSD