GE M60 Instruction Manual page 247

Motor protection system
Hide thumbs Also See for M60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
— This setting selects the source connected to phase current transformers on the power system side
MOTOR LINE SOURCE
of the stator winding.
— This setting selects number of motor start and stop records to average data presented in
NUMBER OF STARTS TO LEARN
the
ACTUAL VALUES  RECORDS  MOTOR LEARNED DATA
MOTOR LOAD AVERAGE CALC. PERIOD
calculated. The calculation is a sliding window.
— This setting enables/disables the two-speed motor function. This function provides proper
2-SPEED MOTOR PROTECTION
protection for a two-speed motor where there are two different full load values. The two-speed functionality is required for
motors having two windings wound into one stator. One winding, when energized, provides one of the speeds. When the
second winding is energized, the motor takes on the speed determined by the second winding. The M60 algorithm
integrates the heating at each speed into one thermal model using a common thermal capacity used register value for
both speeds. Using the M60 for such applications provides several options, allowing the removal of traditional wiring and
interlocking:
Use the M60 front panel pushbuttons and provide necessary operate and interlock logic via FlexLogic
Use external pushbuttons and provide necessary operate and interlock logic using FlexLogic shown as follows
Use a traditional external control schematic with some connections to the M60 for control and protection
— If the two-speed motor feature is used, this setting specifies a FlexLogic operand to indicate the
SPEED2 MOTOR SWITCH
current motor speed. This is typically an indication that the contactor at speed 2 is energized. When the assigned FlexLogic
operand (typically a contact input operand) is asserted, the algorithm switches to speed 2 (high speed). If the assigned
FlexLogic operand is de-asserted, the algorithm switches to speed 1 (low speed). This allows the M60 to determine which
settings are to be active at any given time. To maintain correct motor status indication, the M60 expects a transition from
speed 1 to speed 2 within two seconds; otherwise, the motor status value can be reset.
— This setting specifies the time delay to transfer from high to low speed. This allows the motor to
SPEED2 SWITCH 2-1 DELAY
slow down before energizing at low speed.
— This setting selects source for a motor protection when two-speed motor functionality is used.
SPEED2 MOTOR SOURCE
This can be separate voltage and current banks or one voltage and current bank one with different full load current value
at the second speed (entered in the
are required for speed 2, then order the relay with two CT banks.
— This setting specifies the motor full load current for speed 2.
SPEED2 MOTOR FLA
L1
L2
L3
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
menu.
— This setting specifies the period of time over which parameter averages are
setting). If separate CTs with different ratios or secondary currents
SPEED2 MOTOR FLA
Figure 5-47: Two-speed motor connections
L
H
L
H
L
H
H
H
CT bank 1
H
L
STOP
M60 protection
LOW
HIGH
H
L
T1
T2
T3
MOTOR
T4
T5
T6
CT bank 2
and logic
833723A1.CDR
SYSTEM SETUP
5
5-119