CHAPTER 5: SETTINGS
FLEXLOGIC OPERANDS
STATOR DIFF PKP A
STATOR DIFF SAT A
STATOR DIFF DIR A
FLEXLOGIC OPERANDS
STATOR DIFF PKP B
STATOR DIFF SAT B
STATOR DIFF DIR B
FLEXLOGIC OPERANDS
STATOR DIFF PKP C
STATOR DIFF SAT C
STATOR DIFF DIR C

5.7.5 Power

5.7.5.1 Menu
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  POWER
 POWER
5.7.5.2 Sensitive directional power
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  POWER  SENSITIVE DIRECTIONAL POWER 
DIRECTIONAL POWER 1(2)
 DIRECTIONAL
 POWER 1
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-102: Stator differential final output logic
AND
OR
AND
OR
AND
OR
 SENSITIVE
 DIRECTIONAL POWER
 UNDERPOWER
DIR POWER 1
FUNCTION: Disabled
DIR POWER 1
SOURCE: SRC 1
DIR POWER 1
RCA: 0°
DIR POWER 1
CALIBRATION: 0.00°
DIR POWER 1 STG1
SMIN: 0.100 pu
DIR POWER 1 STG1
DELAY: 0.50 s
DIR POWER 1 STG2
SMIN: 0.100 pu
DIR POWER 1 STG2
DELAY: 20.00 s
DIR POWER 1 BLK:
Off
DIR POWER 1
TARGET: Self-Reset
FLEXLOGIC OPERAND
STATOR DIFF OP A
FLEXLOGIC OPERAND
STATOR DIFF OP B
FLEXLOGIC OPERAND
STATOR DIFF OP C
FLEXLOGIC OPERAND
OR
STATOR DIFF OP
842707A1.CDR
See below
See page 5-194
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: 0 to 359° in steps of 1
Range: 0 to 0.95° in steps of 0.05
Range: –1.200 to 1.200 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: –1.200 to 1.200 pu in steps of 0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic operand
Range: Self-Reset, Latched, Disabled
GROUPED ELEMENTS
5
5-191