CHAPTER 3: INSTALLATION
RELAY SETTINGS:
Not Programmed
The relay can be activated on the front panel or in the EnerVista software.
To activate the relay using the front panel:
1.
Press the
key until the
MENU
2.
Press the
right arrow until the
MESSAGE
3.
Press the
down arrow until the
MESSAGE
4.
Press the
right arrow until the
MESSAGE
SETTINGS
 SETTINGS
 PRODUCT SETUP
5.
After the
RELAY SETTINGS:
"Programmed."
6.
Press the
key to save the change.
ENTER
RELAY SETTINGS:
Not Programmed
7.
When the "NEW SETTING HAS BEEN STORED" message appears, the relay is in "Programmed" state and the "In Service"
LED turns on.
To activate the relay using EnerVista software:
1.
Navigate to Settings > Product Setup > Installation and change the Relay Settings field to "Programmed."
2.
Save the change.

3.7 Install software

3.7.1 EnerVista communication overview

The EnerVista UR Setup software communicates to the relay via the front panel RS232 port or the rear panel RS485 /
Ethernet ports.
To communicate via the RS232 port, use a standard straight-through serial cable. Connect the DB-9 male end to the relay
and the DB-9 or DB-25 female end to the computer COM2 port as described in the CPU Communication Ports section
earlier in this chapter.
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
When the relay is powered up, the "Trouble LED" is on, the "In Service" LED is off, and this message
displays, indicating that the relay is in the "Not Programmed" state and is safeguarding (output
relays blocked) against the installation of a relay whose settings have not been entered. This
message remains until the relay is explicitly put in the "Programmed" state.
header flashes momentarily and the
SETTINGS
message displays.
SECURITY
message displays.
INSTALLATION
RELAY SETTINGS:
 SECURITY
 DISPLAY
 PROPERTIES
 INSTALLATION
Not Programmed message displays, press a
RELAY SETTINGS:
Programmed
PRODUCT SETUP
Not Programmed message displays.
RELAY SETTINGS:
Not Programmed
key to change the selection to
VALUE
NEW SETTING
HAS BEEN STORED
INSTALL SOFTWARE
message displays.
3-53