GE M60 Instruction Manual page 156

Motor protection system
Hide thumbs Also See for M60:
Table of Contents

Advertisement

PRODUCT SETUP
5
5.3.4.2 Serial ports
The M60 is equipped with up to two independent serial communication ports. The faceplate RS232 port is for local use and
is fixed at 19200 baud and no parity. The rear COM2 port is used for either RS485 or RRTD communications.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  SERIAL PORTS
 SERIAL PORTS
It is important that the baud rate and parity settings agree with the settings used on the computer or other equipment that
is connected to these ports.
The RS485 port can be connected to a computer running EnerVista UR Setup. This software can download and upload
setting files, view measured parameters, and upgrade the relay firmware. A maximum of 32 relays can be daisy-chained
and connected to a distributed control system (DCS), power line carrier (PLC), or a computer using the RS485 ports.
The baud rate for standard RS485 communications can be selected as 300, 1200, 2400, 4800, 9600, 14400, 19200, 28800,
33600, 38400, 57600, or 115200 bps.
For the RS485 port, the minimum time before the port transmits after receiving data from a host can be set. This feature
allows operation with hosts that hold the RS485 transmitter active for some time after each transmission.
5-28
 ROUTING
 MODBUS PROTOCOL
PROTOCOL:
DNP 3.0
 DNP PROTOCOL
 DNP / IEC104
 POINT LISTS
 IEC 61850 PROTOCOL
 WEB SERVER
 HTTP PROTOCOL
 TFTP PROTOCOL
 IEC 60870-5-104
 PROTOCOL
 EGD PROTOCOL
 IEC103
 PROTOCOL
COM2 USAGE:
RS485
RRTD SLAVE ADDRESS:
254
RS485 COM2 BAUD
RATE: 19200
RRTD BAUD RATE:
19200
RS485 COM2 PARITY:
None
RS485 COM2 RESPONSE
MIN TIME: 0 ms
See page 5-33
See page 5-36
Range: DNP 3.0, IEC 60870-5-104, IEC 60870-5-103
See page 5-37
See page 5-38
See page 5-41
Access in EnerVista
See page 5-42
See page 5-73
See page 5-73
See page 5-74
See page 5-75
See page 5-77
Range: RS485, RRTD
Range: 1 to 254 in steps of 1. Shown only if the COM2
USAGE setting is "RRTD."
Range: 300, 1200, 2400, 4800, 9600, 14400, 19200,
28800, 33600, 38400, 57600, 115200. Shown only if
the COM2 USAGE is setting is "RS485."
Range: 1200, 2400, 4800, 9600, 19200. Shown only if
the COM2 USAGE is setting is "RRTD."
Range: None, Odd, Even
Range: 0 to 1000 ms in steps of 10
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL