System Board Replacement - Lenovo ThinkSystem SR650 Maintenance Manual

2u rack server
Hide thumbs Also See for ThinkSystem SR650:
Table of Contents

Advertisement

Figure 152. Installing a PHM
a.
Align the triangular marks and guide pins on the processor socket with the PHM; then, insert
the PHM into the processor socket.
Attention: To prevent damage to components, make sure that you follow the indicated
tightening sequence.
b.
Fully tighten the Torx T30 captive fasteners in the installation sequence shown on the heat-sink
label. Tighten the screws until they stop; then, visually inspect to make sure that there is no
gap between the screw shoulder beneath the heat sink and the microprocessor socket. (For
reference, the torque required for the nuts to fully tighten is 1.4 — 1.6 newton-meters, 12 — 14
inch-pounds).
After installing a PHM:
1. Complete the parts replacement. See "Completing the parts replacement" on page 203.

System board replacement

Use this information to remove and install the system board.
S017
.
Chapter 3
Hardware replacement procedures
193