Section 8
Current protection
8.10.3
200
IEC05000465 V2 EN-US
Figure 85:
Typical connection for STBPTOC in 1½-breaker arrangement.

Setting guidelines

The parameters for Stub protection STBPTOC are set via the local HMI or
PCM600.
The following settings can be done for the stub protection.
GlobalBaseSel: Selects the global base value group used by the function to define
IBase, UBase and SBase as applicable.
Operation: Off/On
ReleaseMode: This parameter can be set Release or Continuous. With theRelease
setting the function is only active when a binary release signal RELEASE into the
function is activated. This signal is normally taken from an auxiliary contact
(normally closed) of the line disconnector and connected to a binary input
RELEASE of the IED. With the settingContinuous the function is activated
independent of presence of any external release signal.
1MRK 511 401-UEN A
M12909-3 v5
Bay control REC670 2.2 IEC