Section 8
Current protection
226
Start current of the overcurrent stage: 150% of generator rated current at rated
generator voltage;
Start voltage of the undervoltage stage: 70% of generator rated voltage;
Trip time: 3.0 s.
The overcurrent stage and the undervoltage stage shall be set in the following way:
1.
Set Operation to On.
2.
Set GlobalBaseSel to the right value in order to select the Global Base Values
Group with UBase and IBase equal to the rated phase-to-phase voltage and the
rated phase current of the generator.
3.
Set StartCurr to the value 150%.
4.
Set Characteristic to IEC Def. Time.
5.
Set tDef_OC to 6000.00 s, if no trip of the overcurrent stage is required.
6.
Set VDepFact to the value 100% in order to ensure that the start value of the
overcurrent stage is constant, irrespective of the magnitude of the generator
voltage.
7.
Set Operation_UV to On to activate the undervoltage stage.
8.
Set StartVolt to the values 70%.
9.
Set tDef_UV to 3.0 s.
10. Set EnBlkLowV to Off (default value) to disable the cut-off level for low-
voltage of the undervoltage stage.
The other parameters may be left at their default value.
1MRK 511 401-UEN A
Bay control REC670 2.2 IEC
Application manual