Section 8
Current protection
184
-
×
jX 3R
=
Z
c
n
0
-
+
jX
3R
c
n
EQUATION1946 V1 EN-US
Where
R
is the resistance of the neutral point resistor
n
In many systems there is also a neutral point reactor (Petersen coil) connected to
one or more transformer neutral points. In such a system the impedance Z
calculated as:
= -
Z
jX // 3R // j3X
0
c
n
n
EQUATION1947 V1 EN-US
Where
X
is the reactance of the Petersen coil. If the Petersen coil is well tuned we have 3X
n
this case the impedance Z
Now consider a system with an earthing via a resistor giving higher earth fault
current than the high impedance earthing. The series impedances in the system can
no longer be neglected. The system with a single phase to earth fault can be
described as in Figure 80.
9R X X
=
n
n
c
(
+
×
-
3X X
j3R
3X
n
c
n
n
will be: Z
= 3R
0
0
n
1MRK 511 401-UEN A
)
X
c
Bay control REC670 2.2 IEC
Application manual
(Equation 49)
can be
0
(Equation 50)
= X
In
n
c