Change Lock Chnglck - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 22
Security
22.3
22.3.1
574
Events are also generated:
whenever any setting in the IED is changed.
The internal events are time tagged with a resolution of 1 ms and stored in a list.
The list can store up to 40 events. The list is based on the FIFO principle, that is,
when it is full, the oldest event is overwritten. The list contents cannot be modified,
but the whole list can be cleared using the Reset menu in the LHMI.
The list of internal events provides valuable information, which can be used during
commissioning and fault tracing.
The information can, in addition to be viewed on the built in HMI, also be retrieved
with the aid of a PC with PCM600 installed and by using the Event Monitoring
Tool. The PC can either be connected to the front port, or to the port at the back of
the IED.

Change lock CHNGLCK

Application
Change lock function CHNGLCK is used to block further changes to the IED
configuration once the commissioning is complete. The purpose is to make it
impossible to perform inadvertent IED configuration and setting changes.
However, when activated, CHNGLCK will still allow the following actions that
does not involve reconfiguring of the IED:
Monitoring
Reading events
Resetting events
Reading disturbance data
Clear disturbances
Reset LEDs
Reset counters and other runtime component states
Control operations
Set system time
Enter and exit from test mode
Change of active setting group
The binary input controlling the function is defined in ACT or SMT. The
CHNGLCK function is configured using ACT.
LOCK
Binary input signal that will activate/deactivate the function, defined in ACT or
SMT.
1MRK 511 401-UEN A
GUID-B48775D0-ACF0-49C6-A7F6-69AF37F1C68F v1
GUID-51EEC9C7-8ECF-4546-BC26-326861654340 v4
Bay control REC670 2.2 IEC
Application manual