ABB REC670 Applications Manual page 327

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

1MRK 511 401-UEN A
Bay control REC670 2.2 IEC
Application manual
should take the duration of the breaker closing time of the master into
consideration before sending the breaker closing command. A setting
tWaitForMaster sets a maximum wait time for the WAIT input to reset. If the wait
time expires, the reclosing cycle of the slave is inhibited. If auto reclosing of the
first breaker is unsuccessful, the UNSUCCL output connected to the INHIBIT input
of the slave unit interrupts the auto reclosing sequence of the latter.
The signals can be cross-connected to allow simple changing of the
priority by just setting the High and the Low priorities without
changing the configuration. The input CBCLOSED for each circuit
breaker is important in multi-breaker arrangements to ensure that
the circuit breaker was closed at the beginning of the cycle. If the
High priority circuit breaker is not closed the High priority moves
to the low priority circuit breaker.
Section 14
Control
321