Directional Overpower Protection Goppdop - ABB REC670 Applications Manual

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 8
Current protection
8.13
8.13.1
8.13.2
208
The value of k=0.92 is recommended in generator applications as the trip delay is
normally quite long.
The calibration factors for current and voltage measurement errors are set % of
rated current/voltage:
IAmpComp5, IAmpComp30, IAmpComp100
UAmpComp5, UAmpComp30, UAmpComp100
IAngComp5, IAngComp30, IAngComp100
The angle compensation is given as difference between current and voltage angle
errors.
The values are given for operating points 5, 30 and 100% of rated current/voltage.
The values should be available from instrument transformer test protocols.

Directional overpower protection GOPPDOP

Identification
Function description
Directional overpower protection
Application
The task of a generator in a power plant is to convert mechanical energy available
as a torque on a rotating shaft to electric energy.
Sometimes, the mechanical power from a prime mover may decrease so much that
it does not cover bearing losses and ventilation losses. Then, the synchronous
generator becomes a synchronous motor and starts to take electric power from the
rest of the power system. This operating state, where individual synchronous
machines operate as motors, implies no risk for the machine itself. If the generator
under consideration is very large and if it consumes lots of electric power, it may
be desirable to disconnect it to ease the task for the rest of the power system.
Often, the motoring condition may imply that the turbine is in a very dangerous
state. The task of the reverse power protection is to protect the turbine and not to
protect the generator itself.
IEC 61850
IEC 60617
identification
identification
GOPPDOP
P >
2
DOCUMENT172362-IMG158942
V2 EN-US
1MRK 511 401-UEN A
SEMOD172360-1 v4
SEMOD176574-2 v4
ANSI/IEEE C37.2
device number
32
SEMOD172358-4 v2
Bay control REC670 2.2 IEC
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents