ABB REC670 Applications Manual page 490

Relion 670 series, bay control
Hide thumbs Also See for REC670:
Table of Contents

Advertisement

Section 17
Monitoring
484
220kV Busbar
300/1
100 MVA
242/15,65 kV
Yd5
15 / 0,1kV
100MVA
15,65kV
4000/5
IEC09000041-1-EN V1 EN-US
Figure 209:
Single line diagram for generator application
In order to measure the active and reactive power as indicated in figure 209, it is
necessary to do the following:
1.
Set correctly all CT and VT data and phase angle reference channel
PhaseAngleRef (see Section
PCM600 for analog input channels
2.
Connect, in PCM600, measurement function to the generator CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the
following table:
U
, U
L1L2
P
Q
G
IEC09000041-1-en.vsd
"Setting of the phase reference
1MRK 511 401-UEN A
IED
L2L3
channel") using
Bay control REC670 2.2 IEC
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents