Bay control REC670 2.2 IEC
Application manual
However, in some cases, the following rated secondary currents are used as well:
2A
10A
The IED fully supports all of these rated secondary values.
It is recommended to:
use 1A rated CT input into the IED in order to connect CTs
with 1A and 2A secondary rating
use 5A rated CT input into the IED in order to connect CTs
with 5A and 10A secondary rating
Example on how to connect a star connected three-phase CT set to
the IED
Figure
13
gives an example about the wiring of a star connected two-phase CT set
to the IED. It gives an overview of the actions which are needed to make this
measurement available to the built-in protection and control functions within the
IED as well.
For correct terminal designations, see the connection diagrams
valid for the delivered IED.