1MRK 511 423-UEN A
4.2.2.2
Bay control REC650 2.2 IEC
Application manual
Transformer
I
p
Transformer
I
s
protection
IED
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
IEC05000753 V2 EN-US
Figure 4:
Example how to set CTStarPoint parameters in the IED
Figure
4
shows the normal case where the objects have their own CTs. The settings
for CT direction shall be done according to the figure. To protect the line, direction
of the directional functions of the line protection shall be set to Forward. This
means that the protection is looking towards the line.

Example 2

Two IEDs used for protection of two objects and sharing a CT.
I
I
p
p
I
s
Setting of current input:
Setting of current input:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
Section 4
Analog inputs
Line
Line
Reverse
Forward
Definition of direction
for directional functions
Line protection
IED
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
IEC05000753=IEC05
000753=1=en=Origin
al[1].vsd
SEMOD55055-29 v7