The IEDs may be provided with a function to receive commands either from a
substation automation system or from the local HMI. That receiving function block
has outputs that can be used, for example, to control high voltage apparatuses in
switchyards. For local control functions, the local HMI can also be used. Together
with the configuration logic circuits, the user can govern pulses or steady output
signals for control purposes within the IED or via binary outputs.
Figure
87
shows an application example of how the user can connect
SINGLECMD via configuration logic circuit to control a high-voltage apparatus.
This type of command control is normally carried out by sending a pulse to the
binary outputs of the IED. Figure
operation is performed in a similar way but without the synchro-check condition.
Single
command
function
SINGLECMD
Close CB1
CMDOUTy
IEC04000206 V2 EN-US
Figure 87:
Application example showing a logic diagram for control of a circuit
breaker via configuration logic circuits
Figure
88
and figure
89
On/Off signals. Here, the output is used to control built-in functions or external
devices.
87
shows a close operation. An open breaker
Configuration logic circuits
OUTy
User-
defined
conditions
Synchro-
check
show other ways to control functions, which require steady
Section 8
Control
&
en04000206.vsd
167