ABB 650 series Applications Manual page 60

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

Section 4
Analog inputs
54
132
kV
2
110
V
2
132
kV
2
110
V
2
IEC16000140 V1 EN-US
Figure 18:
A two phase-to-earth connected VT
Where:
1)
shows how to connect three secondary phase-to-earth voltages to three VT inputs on
the IED
2)
is the TRM where these three voltage inputs are located. For these three voltage
inputs, the following setting values shall be entered:
VTprim = 132 kV
VTsec = 110 V
Inside the IED, only the ratio of these two parameters is used. It shall be noted that the
ratio of the entered values exactly corresponds to ratio of one individual VT.
66
66
=
110
110
EQUATION1903 V1 EN-US
Table continues on next page
L1
IED
L2
1
3
3
1MRK 511 423-UEN A
2
3
SMAI2
BLOCK
AI2P
^GRP2L1
AI1
5
^GRP2L2
AI2
^GRP2L1L2
AI3
^GRP2N
AI4
AIN
4
IEC16000140-1-en.vsdx
(Equation 2)