Section 10
Monitoring
10.2.3
204
input signal to the function. The function generates alarms based on the received
information.

Setting guidelines

The parameters for Gas medium supervision SSIMG can be set via local HMI or
Protection and Control Manager PCM600.
Operation: This is used to disable/enable the operation of gas medium supervision
i.e. Off/On.
PresAlmLimit: This is used to set the limit for a pressure alarm condition in the
circuit breaker.
PresLOLimit: This is used to set the limit for a pressure lockout condition in the
circuit breaker.
TempAlarmLimit: This is used to set the limit for a temperature alarm condition in
the circuit breaker.
TempLOLimit: This is used to set the limit for a temperature lockout condition in
the circuit breaker.
tPressureAlarm: This is used to set the time delay for a pressure alarm indication,
given in s.
tPressureLO: This is used to set the time delay for a pressure lockout indication,
given in s.
tTempAlarm: This is used to set the time delay for a temperature alarm indication,
given in s.
tTempLockOut: This is used to set the time delay for a temperature lockout
indication, given in s.
tResetPressAlm: This is used for the pressure alarm indication to reset after a set
time delay in s.
tResetPressLO: This is used for the pressure lockout indication to reset after a set
time delay in s.
tResetTempLO: This is used for the temperature lockout indication to reset after a
set time delay in s.
tResetTempAlm: This is used for the temperature alarm indication to reset after a set
time delay in s.
1MRK 511 423-UEN A
GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v2
Bay control REC650 2.2 IEC
Application manual