EMC Directive related standards
■ Emission requirements
Standard: EN61131-2:2007
Test item
CISPR16-2-3
*2
Radiated emission
CISPR16-2-1, CISPR16-1-2
*2
Conducted emission
*1 QP: Quasi-Peak value, Mean: Average value
*2 Programmable controller is an open-type device and must be placed in a conductive control panel or similar type of enclosure. The tests
were conducted with the programmable controller installed in a control panel, applying the maximum rated input voltage of the power
supply module.
■ Immunity requirements
Standard: EN61131-2:2007
Test item
EN61000-4-2
*1
Electrostatic discharge immunity
EN61000-4-3
Radiated, radio-frequency,
*1
electromagnetic field immunity
EN61000-4-4
*1
Fast transient burst immunity
EN61000-4-5
*1
Surge immunity
EN61000-4-6
*1
Conducted RF immunity
EN61000-4-8
Power-frequency magnetic field
*1
immunity
EN61000-4-11
Voltage dips and interruptions
*1
immunity
*1 Programmable controller is an open-type device and must be placed in a conductive control panel or similar type of enclosure. The tests
were conducted with the programmable controller installed in a control panel.
*2 The accuracy of an analog-digital converter module may temporarily vary within 10%.
Test description
The electromagnetic wave emitted by
the product to the external space is
measured.
The noise level which the product
emits to the power line is measured.
Test description
An electrostatic discharge is applied
to the enclosure of the equipment.
An electric field is radiated to the
product.
Burst noise is applied to power lines
and signal lines.
Lightning surge is applied to power
lines and signal lines.
High-frequency noise is applied to
power lines and signal lines.
The product is immersed in the
magnetic field of an induction coil.
Power voltage is momentarily
interrupted.
Value specified in standard
• 30 to 230MHzQP: 40dBV/m (measured at 10m distance)
• 230 to 1000MHzQP: 47dBV/m (measured at 10m distance)
• 0.15 to 0.5MHzQP: 79dB, Mean: 66dB
• 0.5 to 30MHzQP: 73dB, Mean: 60dB
Value specified in standard
• 8kV: Air discharge
• 4kV: Contact discharge
80% AM modulation @1kHz
• 80 to 1000MHz: 10Vm
• 1.4 to 2.0GHz: 3Vm
• 2.0 to 2.7GHz: 1Vm
• AC/DC power, I/O power, and AC I/O (unshielded) lines: 2kV
• DC I/O, analog, and communication lines: 1kV
• AC power, AC I/O power, and AC I/O (unshielded) lines: 2kV CM, 1kV DM
• DC power and DC I/O power lines: 0.5kV CM, 0.5kV DM
*2
• DC I/O, AC I/O (shielded), analog
0.15 to 80MHz,
80% AM modulation @1kHz, 10Vrms
50/60Hz, 30A/m
• 0%, 0.5 periods, starting at zerocrossing
• 0%, 250/300 periods (50/60Hz)
• 40%, 10/12 periods (50/60Hz)
• 70%, 25/30 periods (50/60Hz)
Appendix 6 EMC and Low Voltage Directives