Allocation image of remote devices
RX/RY 1 occupied station
100
13F
Allocation image of remote devices
RX/RY 2 occupied station
100
17F
11 - 8
11.5 Device Range that Can Be Set
POINT
POINT
POINT
Remote device setting of the GOT (slave station)
In the GOT, the device range that is allocated to itself is stored as the number of the occupied
stations from the first device number. Images for device allocation at the master station side and
GOT (slave station) side are shown below.
Note that in the allocation image of the remote device, RX/RY 1 occupied station, the remote
device that works for the GOT (slave station) at the master station is set to RX100 to RX13F and
RY100 to RY13F, but the corresponding remote device at the GOT is set to RX000 to RX03F and
RY000 to RY03F.
Master station
GOT (slave station)
RX/RY
RX/RY
Master station
GOT (slave station)
RX/RY
RX/RY
Allocation image of remote devices
Ww/Wr 1 occupied station
Master station
Ww/Wr
000
03F
100
11F
Allocation image of remote devices
Ww/Wr 2 occupied station
Master station
Ww/Wr
000
100
07F
13F
GOT (slave station)
Ww/Wr
000
01F
GOT (slave station)
Ww/Wr
000
03F