5.3
Connection Diagram
The following diagram shows the connection between the GOT and the PLC.
5.3.1
RS-232 cable
■1. Connection diagram
(1) RS-232 connection diagram 1)
*1
Some MODBUS/RTU equipment require the control line (CS, RS, etc.) to be controlled.
Make sure to connect the cables and wires as described in the MODBUS/RTU equipment manual.
(2) RS-232 connection diagram 2)
*1
Some MODBUS/RTU equipment require the control line (CS, RS, etc.) to be controlled.
Make sure to connect the cables and wires as described in the MODBUS/RTU equipment manual.
■2. Precautions when preparing a cable
(1) Cable length
The length of the RS-232 cable must be 15m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
(3) MODBUS equipment side connector
Use the connector compatible with the MODBUS/RTU equipment side module.
For details, refer to the MODBUS/RTU equipment user's manual.
GOT side
1
CD
RD(RXD)
2
3
SD(TXD)
4
ER(DTR)
SG
5
6
DR(DSR)
7
RS(RTS)
CS(CTS)
8
9
NC
GOT side
SD
RD
ER
DR
SG
RS
CS
*1
MODBUS equipment side
-
TxD
RxD
-
SG
-
-
-
-
*1
MODBUS equipment side
RxD
TxD
-
-
SG
-
-
5.3 Connection Diagram
5
5 - 5