5.6

Device Range that Can Be Set

The device ranges of controller that can be used for GOT are as follows.
Note that the device ranges in the following tables are the maximum values that can be set in GT Designer3.
The device specifications of controllers may differ depending on the models, even though belonging to the same series.
Please make the setting according to the specifications of the controller actually used.
When a non-existent device or a device number outside the range is set, other objects with correct device settings may not
be monitored.
■1. Setting item
Item
Set the device name, device number, and bit number.
The bit number can be set only when specifying the bit of word device.
Device
File No.
Information
Displays the device type and setting range which are selected in [Device].
Set the station number of the controller to be monitored.
All
Host
Network
Other
■2. Function Code
The GOT supports the following function codes.
Function Code
0x01
0x02
0x03
0x04
0x05
0x06
0x0F
0x10
0x14
0x15
5 - 16
5.6 Device Range that Can Be Set
Set the file No.
The file No. can be set only when select 6 at [Device].
Select this item for writing data to all controllers connected. During monitoring, the host controller is monitored.
(When writing the data in numerical input, the data is written to all connected controllers during input, and the
host controller is monitored during other than input (displaying).)
Select this item for monitoring the host controller.
Select this for monitoring other controllers.
After selecting the item, set the station number and network number of the controller to be monitored.
NW No.: For the MODBUS/RTU connection, set "1".
For the MODBUS/TCP connection, set the network No.
Station No.: Set the station No.
Read Coils
Read Discrete Inputs
Read Holding Registers
Read Input Registers
Write Single Coil
Write Single Register
Write Multiple Coils
Write Multiple Register
Read File Record
Write File Record
Description
Function
Number of device that is accessible
with one message
[Unit: point(s)]
1 to 2000
1 to 2000
1 to 125
1 to 125
1
1
1 to 1968
1 to 123
1 to 124
1 to 122