10.3.2 GOT Side Settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: AB
• Controller Type: Control/CompactLogix
• I/F: Interface to be used
• Driver: EtherNet/IP(AB), Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
11.3.2 ■ Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
1.1.2 I/F communication setting
Communication detail settings
Make the settings according to the usage environment.
(1) GT16, GT14
3.
4.
Item
GOT NET No.
GOT PLC No.
GOT
Click!
IP Address
Subnet
*1
Mask
Default
*1
Gateway
Ethernet
Download Port
*1
No.
GOT
Communication
Port No.
Retry
Startup Time
Timeout Time
Delay Time
10. CONNECTION TO ALLEN-BRADLEY PLC
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
*2
(Default: 1)
Set the IP address of the GOT.
*1
(Default: 192.168.3.18)
Set the subnet mask for the sub
network.(Only for connection via
router)
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the default
gateway where the GOT is
connected.(Only for connection via
router)
(Default: 0.0.0.0)
Set the GOT port No. for Ethernet
download.
(Default: 5014)
Set the GOT port No. for the
connection with the Ethernet module.
(Default: 5015)
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
10.3 Ethernet Connection
9
10
11
Range
1 to 239
12
1 to 64
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
13
0.0.0.0 to
255.255.255.255
1024 to 5010,
14
5014 to 65534
(Except for 5011,
5012, 5013, 44818
and 49153)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013, 44818
and 49153)
15
0 to 5times
3 to 255sec
16
3 to 90sec
0 to 10000
(
10 ms)
10 - 15