(2) AB MicroLogix
Item
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 19200bps)
Specify the format in which the sum
check is performed during
Sum Check Type
communication when performing sum
check.
(Default: BCC)
Specify the adapter address (station
No. of the PLC that the GOT will
*1
Adapter Address
monitor) in the connected network.
(Default: 0)
Specify the host address (station No.
of the adapter to which the GOT is
*1
Host Address
connected) in the connected network.
(Default: 1)
*1
Do not specify the same value for the adapter address and
host address.
10 - 10
10. CONNECTION TO ALLEN-BRADLEY PLC
10.2 Serial Connection
Description
Range
4800bps,
9600bps,
19200bps,
38400bps
BCC, CRC16
0 to 63
0 to 63
(3) AB Control/CompactLogix
Item
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 19200bps)
Set this item when change the data
length used for communication with
Data Bit
the connected equipment.
(Default: 8bits)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
Parity
during communication.
(Default: None)
Specify the format in which the sum
check is performed during
Sum Check Type
communication when performing sum
check.
(Default: BCC)
Set the number of retries to be
performed when a communication
Retry
error occurs.
(Default: 3times)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Specify the adapter address (station
No. of the PLC that the GOT will
Adapter Address
monitor) in the connected network.
(Default: 0)
Specify the host address (station No.
of the adapter to which the GOT is
Host Address
connected) in the connected network.
(Default: 0)
Set this item to adjust the
transmission timing of the
Delay Time
communication request from the
GOT.
(Default: 0ms)
Description
Range
9600bps,
19200bps,
38400bps,
57600bps
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
BCC,
CRC16
0 to 5times
3 to 30sec
0 to 254
0 to 254
0 to 300ms