Ems/Communication Events; Single Fault Events - Samsung ELSR362-00004 Installation Manual

Res 3.6 kwh all in one
Hide thumbs Also See for ELSR362-00004:
Table of Contents

Advertisement

Type
PROTECTION

9.1.7 EMS/Communication Events

Type
WARNING
WARNING
WARNING
WARNING

9.1.8 Single Fault Events

Type
WARNING
Australia (Eng.) 05/2015. Rev1.1
Code
Description
E514
CELL
TEMPERATURE
SENSOR 2EA
[Table 9-6: BMS general events list]
Code
Description
E601
INVERTER
COMMUNICATION
EVENT
E602
ETHERNET
EVENT
E603
ENERGY METER
EVENT
C128
Ethernet Error
[Table 9-7: EMS/communication events list]
Code
Description
E701
GRID UNDER
VOLTAGE FAULT
E702
GRID OVER
VOLTAGE FAULT
E703
GRID UNDER
FREQUENCY
FAULT
E704
GRID OVER
FREQUENCY
FAULT
9. Problem Confirmation
Measures
Occurs above the standard battery cell
temperature.
Measures
Turn off and restart the system.
Reconnect the communication line
between the EMS board and the DSP board.
Disconnect and reconnect the LAN.
Turn off and restart the Router.
Make sure that the DHCP server function of
Router is activated.
Turn off and restart the system.
Make sure that the Meter device is properly
selected.
Disconnect and reconnect the D0 cable.
Turn off and restart the system.
Make sure that the Ethernet communication
port and wire connected properly.
Measures
The operation mode is terminated when a
power system event occurs. Restart 1
minute after the electric power system
event is settled.
The operation mode is terminated when a
power system event occurs. Restart 1
minute after the electric power system
event is settled.
The operation mode is terminated when a
power system event occurs. Restart 1
minute after the electric power system
event is settled.
The operation mode is terminated when a
power system event occurs. Restart 1
minute after the electric power system
77