Reconditioning The Fixed Contact; Lubricating The Interrupter Unit - GE GL 311 F3/4031 P/VE Operating Instructions Manual

High voltage circuit breaker
Hide thumbs Also See for GL 311 F3/4031 P/VE:
Table of Contents

Advertisement

10.1.6

Reconditioning the Fixed Contact

10.1.7

Lubricating the Interrupter Unit

REV7
/REV7
• Replace the guide strip (12). The guide strip is located in a
dovetail groove. It is therefore necessary to overcome
mechanical resistance when replacing it.
12
12
Guide strip, 3x5x380 (GK)
• Unpack and grease a new interrupter unit (5).
- Lubricate the outer diameter of the interrupter unit in the area of
the electrical sliding contact surface per lubrication specification
L6.
- Grease the entire length of the interrupter tube in the interrupter
unit per lubrication specification L7.
L7
5
Interrupter unit
OI 250 (EN)
R
ECONDITIONING
5
L6 L6
1x
1x
87 / 146

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gl 312 f3/4031 p/ve

Table of Contents