Connecting The Drive Rod To The Drive Lever - GE GL 311 F3/4031 P/VE Operating Instructions Manual

High voltage circuit breaker
Hide thumbs Also See for GL 311 F3/4031 P/VE:
Table of Contents

Advertisement

I
NSTALLATION
6.9.3

Connecting the Drive Rod to the Drive Lever

42 / 146
• Lubricate the flanged coupling pin (14) as per L2.
• Connect the drive rod (5) and the drive lever (4) using the flanged
coupling pin (14), while maintaining the installation position of the
drive rod. The side of the drive rod with the hexagon nut faces
Pole B.
• Apply locking adhesive S1 to the screw (13).
• Lock the flanged coupling pin (14) using the locking sleeve (11),
washer (12) and screw (13). Tighten to a torque of 7Nm.
2
2
Pole B
4
Drive lever
5
Drive rod
11
Locking sleeve
12
Washer, 6 A2
13
Hexagon screw, M6x16 A2-70
14
Flanged coupling pin, 16x68
OI 250 (EN)
5
4
12
13
14
11
1x
1x
1x
1x
1x
1x
1x
REV7