Connecting The Operating Mechanisms And Pole Columns - GE GL 311 F3/4031 P/VE Operating Instructions Manual

High voltage circuit breaker
Hide thumbs Also See for GL 311 F3/4031 P/VE:
Table of Contents

Advertisement

6.9.4

Connecting the Operating Mechanisms and Pole Columns

REV7
/REV7
• Lubricate the shaft of pole B as per L2.
• Fit lever B (6) onto the shaft of pole B (2).
• Apply locking adhesive S1 to the screw (9). Secure the lever with
the screw (9) and washer (10).
Tighten to a torque of 35 Nm.
• Insert the drive rod (5) into lever B (6).
• Turn lever B (6) in the direction of the arrow until the lever and the
shaft are in contact with one another. This reduces the clearance
between the lever and the shaft.
• Pull on the drive rod to reduce the clearance between the drive
shaft and operating lever.
• Check to make sure the holes in the lever and drive rod are
aligned. If required align the pole columns using a tire lever. (see
"Aligning the Pole Columns Using a Tire Lever (if required)"
on Page 44)
2
10
14
9
12
15
11
6
13
2
Pole
5
Drive rod
6
Lever
9
Hexagon screw, M10x25 A2-70
10
Washer, 50.5/11/3
11
Locking sleeve
12
Washer, 6 A2
13
Hexagon screw, M6x16 A2-70
14
Flanged coupling pin, 16x68
15
Sleeve
OI 250 (EN)
I
NSTALLATION
5
43 / 146
1x
1x
1x
1x
1x
1x
1x
1x
1x
1x