Removing the Double Motion System

84 / 146
• Remove eight screws (3) and washers (4) from the upper flange
of the chamber insulator (1).
• Carefully remove the double motion system (2).
1
Chamber insulator
2
Double motion system
3
Hexagon screw, M12x45 A2-70
4
Washer, 12x40 A2
OI 250 (EN)
4
3
2
1
1x
1x
8x
8x
REV7