Manually Charging The Closing Spring - GE GL 311 F3/4031 P/VE Operating Instructions Manual

High voltage circuit breaker
Hide thumbs Also See for GL 311 F3/4031 P/VE:
Table of Contents

Advertisement

C
OMMISSIONING
7.6.6

Manually Charging the Closing Spring

62 / 146
• Check the operating state of the circuit breaker and the
mechanism:
- Closing spring discharged.
- Breaker either in closed or open position.
- Control voltage disconnected.
• Open the door of the mechanism.
• Using the hand crank (70.53), turn the gearing clockwise until the
spring position indicator shows "closing spring charged".
• In this position the gearing is in idling position and can be turned
further.
• While the closing spring is being charged, the return stop
prevents the crank wheel from slipping backwards when manual
charging is interrupted or stopped.
• Close the cabinet door.
OI 250 (EN)
REV7
/REV6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gl 312 f3/4031 p/ve

Table of Contents