When using the power vent system, direction of flow through the vents can be up, down, horizontal or diagonal since the system
is sealed and vacuumed. The vent restrictor level should be set based on length in feet, number of elbows and the vent
termination.
NOTE: A minimum of 12 feet of venting is required between the fireplace and the in-line power vent. Do not use the power vent
if the vent routing is less than 12 feet. Refer to the
Clearance - Clearances between the vent pipe and combustible materials must be maintained at 3" inches top and 1" for side
and below. Maintain the same clearance from the power vent box to any combustible materials.
Power vent unit must be installed by a qualified installer in accordance with these instructions.
CAUTION! Failure to install, operate, and maintain the power venting system in accordance with manufacturer's instructions
will result in conditions which may produce bodily injury and/or property damage
48 |
P a g e
Flare Power Vent Installation Manual
for more specific
instructions.