Ignition transformers TZI, TGI

Technical Information · GB
8 Edition 06.16
• Electrical ignition of gas burners
• Ignition and burner control with a single electrode possible
• TZI 7,5-20/33R complies with CSA

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell Kromschroder TZI Series

  • Page 1: Ignition Transformers Tzi, Tgi

    Industrial & Commercial Thermal Ignition transformers TZI, TGI Technical Information · GB 8 Edition 06.16 • Electrical ignition of gas burners • Ignition and burner control with a single electrode possible • TZI 7,5-20/33R complies with CSA...
  • Page 2: Table Of Contents

    Contents Ignition transformers TZI, TGI . . . . . . . . . . . . . . . . . . . . . . . 1 Contents .
  • Page 3: Application

    Application TZI 5-15/100, TZI 7-25/20, TZI 7,5-12/100, TZI 7,5-20/33 1 Application Ignition transformers TZI and TGI are designed for high-voltage spark ignition of gas burners and gas- ignited or directly ignited oil burners. The ignition transformers can also be used on burners with single- electrode operation;...
  • Page 4 Application Bogie hearth forging furnace Intermittent shuttle kiln Walking beam furnace in the metallurgical industry in the ceramics industry with overhead firing TZI, TGI · Edition 06.16...
  • Page 5: Examples Of Application

    Application 1 .1 Examples of application 1 .1 .1 Double-electrode operation IFD 258 Ignition using ignition electrode Ignition transformer TGI is supplied with voltage via the automatic burner control unit IFD 258. The ignition transformer generates a high voltage. This high voltage creates ignition sparks between the ignition electrode BIO/ and burner ground.
  • Page 6: Certification

    Certification 2 Certification Ignition transformers TZI and TGI are built for applica- tions pursuant to the Machinery Directive 2006/42/EC. TZI 7,5-20/33R Complies with Canadian Standards Association CSA C22.2 No. 13-1962. TZI, TGI · Edition 06.16...
  • Page 7: Function

    Function 3 Function 3 .1 Connection diagrams Ignition: double-electrode operation gn/ye Ignition: single-electrode operation Burner control unit Single-electrode operation is possible only in conjunc- tion with suitable automatic burner control units. The switchover between ignition and monitoring is per- formed by the automatic burner control unit. gn/ye High-voltage connection ∅...
  • Page 8: Selection

    Selection 4 Selection 4 .1 Selection table TZI 5-15/100   TZI 7-25/20   TZI 7,5-12/100   TZI 7,5-20/33   TGI 5-15/100   TGI 7-25/20   TGI 7,5-12/100   TGI 7,5-20/33   Order example TZI 5-15/100W ...
  • Page 9: Project Planning Information

    Project planning information 5 Project planning information 5 .3 Cable selection Use mains cable suitable for the type of operation and 5 .1 Operation complying with local regulations. The ignition transformers are suitable only for applica- Install an equipotential bond (4 mm , compliant with tions for igniting gas burners and gas-ignited or directly local regulations) between burner and ignition trans-...
  • Page 10: Reduction Of Emc, Wiring

    Project planning information 5 .4 Reduction of EMC, wiring Avoid external electrical interference. Lay cables individually and, if possible, not in a metal conduit. Do not lay UV/ionization cable and ignition cables to- gether and lay them as far apart as possible. Screw the ignition cable securely into the high-voltage connection on the ignition transformer and run to the burner by the shortest possible route, see page 7...
  • Page 11: Duty Cycle

    Project planning information 5 . 7 Duty cycle Example Ignition transformer TZI 7-25/20W with a duty cycle of The duty cycle indicates for how long the ignition trans- 20% for an ambient temperature of -20 to +35°C. former can be switched on within 180 s, without it be- ing overloaded.
  • Page 12: Accessories

    Accessories 6 Accessories 6 .1 High-voltage cable FZLSi 1/7 -50°C (-58°F) to 180°C (356°F), Order No. 04250410, FZLK 1/7 -5°C (23°F) to 80°C (176°F), Order No. 04250409. 6 .2 Radio interference suppressed electrode adapters Plug cap, 4 mm (0.16 inch), interference-suppressed, Order No.
  • Page 13: Technical Data

    Technical data 7 Technical data Type Input Output Duty cycle** Enclosure Weight V AC TZI 5-15/100W 50 (60) 0.45 (0.35) 5000 (11) IP 00 TZI 7-25/20W 50 (60) (0.8) 7000 (18) IP 00 TZI 7,5-12/100W 50 (60) (0.45) 7500 IP 00 TZI 7,5-20/33W 50 (60) (0.7)
  • Page 14: Dimensions

    Technical data 7 .1 Dimensions Length of connection cable: approx. 410 mm TZI 5-15/100, TZI 7-25/20 TZI 7,5-12/100, TZI 7,5-20/33 ∅ 5.0 M20 (A/F 27) M20 (A/F 24) TZI, TGI · Edition 06.16...
  • Page 15: Feedback

    Feedback Feedback Finally, we are offering you the opportunity to assess this “Technical Information (TI)” and to give us your opinion, so that we can improve our documents further and suit them to your needs. Clarity Comprehension Scope Found information quickly Coherent Too little Too complicated...