Download Print this page

Optional Kits - Cisco ONS 15454 Unpacking And Installing

Four-shelf and zero-shelf bay assembly
Hide thumbs Also See for ONS 15454:

Advertisement

Verify Office Power
Using a voltmeter, verify the office battery and ground at the following points on the fuse and alarm
Step 1
panel:
a.
b.
For a 100A fuse panel, insert a 30A fuse into the fuse position according to site practice.
Step 2
Using a voltmeter, verify the shelf for -48VDC battery and ground:
Step 3
a.
b.

Optional Kits

There are four optional kits that can be ordered separately as needed for cable protection, aisle guards,
and supplementary installation components. This section lists the kits by product name, title, and part
number and provides descriptions for each kit.
Table 2
Product Name
15454-BAY-EXT=
15454-BAY-COVER=
15454-BAY-GUARD=
15454-BAY-ACC1=
78-13271-05
To verify the power, place the black test lead of the voltmeter to the frame ground. Place the red test
lead on the A-side connection and verify that it is between -42VDC and -57VDC. Place the red test
lead on the B-side connection and verify that it is between -42VDC and -57VDC.
To verify the ground, place the black test lead of the voltmeter to the frame ground. Place the red
test lead on the A-side return ground and verify that no voltage is present. Place the red test lead on
the B-side return ground and verify that no voltage is present.
To verify the A-side of the shelf, place the black lead of the voltmeter to the frame ground. Place the
red test lead to the BAT1 (A-side battery connection) red cable. Verify it reads between -42VDC and
-57VDC. Then place the red test lead of the voltmeter to the RET1 (A-side return ground) black
cable and verify that no voltage is present.
To verify the B-side of the shelf, place the black test lead of the voltmeter to the frame ground. Place
the red test lead to the BAT2 (B-side battery connection) red cable. Verify it reads between -42VDC
and -57VDC. Then place the red test lead of the voltmeter to the RET2 (B-side return ground) black
cable and verify that no voltage is present.
Optional Kits
Title
15454 Bay Extender Kit (2.38-inch)
15454 Bay End Plate Cover Kit
15454 Bay End Guard Kit
15454 First Aid Kit
Unpacking and Installing the Cisco ONS 15454 Four-Shelf and Zero-Shelf Bay Assembly
Optional Kits
Part Number
74-2794-01
74-2795-01
74-2796-01
53-2073-01
33

Advertisement

loading