Figure 146. Inhibit menu
Use the
switches to inhibit alarms by selecting Inhibit On
with the
. The confirmation screen appears.
Figure 147. Confirm Inhibit On screen
Select
to place the transmitter alarms into inhibit mode. Select
will cancel the choice and leave the alarms in normal operating
mode.
Figure 148. Confirm Inhibit Off screen
To return from Inhibit mode to to the normal monitoring mode,
select Inhibit Off
with the
Select
to remove the transmitter from Inhibit mode. Select 'X"
to cancel the choice and leave the alarms in Inhibit mode.
Installation and Operation
. A confirmation screen appears.
Figure 149. Inhibit Status screen
When the transmitter is in Inhibit mode, the General Status
display will display the inhibit icon
Force mA Output
CAUTION
!
Caution: The mA output set in this menu will revert to the normal operating values
when exiting the Test Menu. For more information on setting the mA output levels for
normal operation, see
mA
Levels.
Force mA Output allows peripheral devices driven by mA output
from the transmitter to be tested. Based on the mA output
values set in the mA Levels option (see
chooses the mA level to output to the device.
Figure 150. Force mA Output screen
The New mA Output screen shows the current mA output in the
left column. The output can be controlled by changing the value
in the column on the right.
88
.
mA
Levels), the operator