Honeywell XNX-AM Series Technical Manual page 133

Hide thumbs Also See for XNX-AM Series:
Table of Contents

Advertisement

XNX Universal Transmitter
Appli-
Fault
Description
cable
Sensors
Option Part Num-
F159
All
ber Mismatch
Hardware Diagnos-
F160
ECC, mV
tic Failure
mA Input Indicates
Optima,
F161
Fault
Excel
Error reloading
F162
safety critical RAM
All
block
Interrupt integrity
F163
All
fault
F164
mV Sensor failure
mV
Warnings/Faults
Latching / Non-
Frequency of
Latching
Diagnostic
Only at powerup
or every 125 ms
Non-latching
when no option
board detected
Non-latching
Main loop x2
Non-latching
1 second
Non-latching
2 seconds
Non-latching
Main loop
Latching
1 second
Event History Data
Check that installed option matches the option indicated in the XNX part
Entire option part #
number, check wiring to Optima/Excel.
Gain1 high byte,
Replace defective EC cartridge or mV personality board.
Gain2 low byte
Indicates mA input from Optima/Excel is below 1 mA, indicating a fault in
the sensor. Any other fault will also trigger this fault, so check for addi-
Input mA
tional faults in event history to determine specific issue. If no other faults
indicated, check wiring between Optima/Excel and XNX. Also check that
switches S3 and S4 are set correctly.
Note 3
Contact Honeywell Analytics' Service Department.
Note 3
XNX will reset if more than 600,000 successive errors occur.
mV bridge voltage or
Indicates that the sensor was changed or is bad. If the fault will not clear,
bridge current that
replace the sensor.
caused fault