XNX Universal Transmitter
Set Temperature Warning
WARNING
!
Warning: There is a potential loss of sensitivity when the sensor is exposed to the
extreme low and/or high temperature. Please check each sensor's recommended
operating temperature and sensitivity loss before disabling temperature warning.
The Set Temperature Warning option allows the temperature
warning to be enabled or disabled. By default, this option is enabled.
In the Range & Alarms menu, use the
Temperature Warning menu. Select
When entering Set Temperature Warning menu, a message
will be displayed either "DISABLE WARNING?" or "ENABLE
WARNING?" per the current setting. User will select disable or
enable temperature warning.
Qu
Qu
estion message when current
"
setting is "ENABLE
setting is "DISABLE
Installation and Operation
controls to select
to enter the menu.
estion message when current
"
Set Deadband
The Set Deadband menu allows enabling and disabling of the
reading deadband. The deadband is a range of value where the
gas reading is displayed as zero.
In the Range & Alarms menu, use the
Deadband menu. Select
When entering Set Deadband menu, a message will be displayed
either "DEADBAND OFF" or "DEADBAND ON" per the current
setting. User will select deadband off or on.
Qu
estion message when current
N"
setting is "DEADBAND O
Note: When deadband is off and the gas reading is between 0 and
negative fault, XNX mA output will be ranged between 4 mA and
2.4 mA.