Honeywell XNX-AM Series Technical Manual page 113

Hide thumbs Also See for XNX-AM Series:
Table of Contents

Advertisement

XNX Universal Transmitter
4. Follow the procedure in the
Sensors, mV Sensors, and Searchpoint Optima
both zero and span calibrations.
5. Apply the target gas to the sensor. Pass the gas through the flow
housing at a rate of 300-700 ml/min.
6. Calibrate sensors at concentrations representative of those to
be measured. When feasible, calibrate the sensor with the target
gas it is to detect.
7. Ensure that the sensor and the vicinity around it is clear of all
traces of the calibration gas before continuing. This is to avoid
triggering spurious alarms. If the calibration fails at any point,
discard the cartridge and replace it with a new one (see the
MPD Sensor Cartridge Replacement
8. Remove the test equipment, refit the weatherproof cap to the
sensor (if it was previously removed for the test), and return the
system to normal operation.
MPD Flammable Sensor Operational Life
The pellistors used in flammable gas sensors can suffer from a loss of
sensitivity when in the presence of poisons or inhibitors, e.g., silicones,
sulfides, chlorine, lead, or halogenated hydrocarbons. The pellistors
are poison-resistant to maximize the operational life of the flammable
sensor. The typical operating life of the pellistor sensor used in the
MPD-CB1 is 60 months.
Section 3 - Calibration
Zero and Span Calibration for EC
section for
section) .
Cross-calibration Procedure for MPD-CB1
CAUTION
!
Caution: When a user calibrates a sensor using a different gas, the responsibility for identifying and
recording the calibration rests with the user. Refer to local regulations where appropriate.
When the MPD-CB1 Combustible LEL sensor is to be calibrated with a
gas which is different from the gas or vapor to be detected, follow this
cross-calibration procedure:
These star rating tables list the gases according to the reaction they
produce at a given detector.
Star
Gas
Rating
Acetone
4*
Ammonia
7*
Benzene
3*
Butanone
3*
Butane
4*
Butyl acetate
1*
Butyl acrylate
1*
Cyclohexane
3*
Cyclohexanone
1*
Diethyl ether
4*
An eight-star (8*) gas produces the highest output, while a one-star (1*)
gas produces the lowest. (These are not applicable at ppm levels.)
To cross-calibrate the MPD-CB1 combustible gas sensor:
111
Star
Gas
Rating
Ethane
6*
Nonane
Ethanol
5*
Octane
Ethyl acetate
3*
Pentane
Ethylene
5*
Propane
Heptane
3*
Propan-2-ol
Hexane
3*
Styrene
Hydrogen
6*
Tetra hydrafuran
Methane
6*
Toluene
Methanol
5*
Triethylamine
MIBK
3*
Xylene
Star
Gas
Rating
2*
3*
4*
5*
4*
2*
4*
3*
3*
2*