XNX Universal Transmitter
Appli-
Fault
Description
cable
Sensors
Internal 4-20 mA
monitoring circuit
F149
All
communication
failure
mA Output Monitor
F150
Communications
All
Watchdog Error
Sensor Module
F151
ECC
Type Changed
Option Module
F152
All
Configuration Error
Signal/Data mis-
Optima,
F153
match error on IR
Excel
personality
mA Input Diagnos-
Optima,
F154
tic Failure
Excel
Generic mA Sensor
Generic
F155
Type Error
mA
mV Current Control
F156
mV
Failure
F157
Sensor Drift Fault
ECC, mV
Sensor/Personal-
F158
ity Part Number
All
mismatch
Warnings/Faults
Latching / Non-
Frequency of
Latching
Diagnostic
Non-latching
3.366 seconds
Non-latching
138 us
Non-latching
2 seconds
Only at powerup
or every 125 ms
Latching
when no option
board detected
Non-latching
2 seconds
5 minutes after
power up and
Latching
then every 8
hours
Non-latching
2 seconds
Non-latching
Main loop x16
Non-latching
2 seconds
"ECC & mV: main
loop x2;
Non-latching
Optima & Excel: 2
seconds"
Event History Data
0
Contact Honeywell Analytics' Service Department.
Communication error
Contact Honeywell Analytics' Service Department.
count
Module type: 0=None,
For ECC: Perform Accept New Sensor function, if problem persists
1=ECC, 2=mV,
contact Honeywell Analytics' Service Department. For others, contact
3=Excel, 4=Optima,
Honeywell Analytics' Service Department.
5=Generic mA
Option module ID:
0=None, 1=Founda-
Confirm option properly installed, reconfigure unit.
tion Fieldbus, 2=Mod-
bus, 3=Relay
Check wiring to Optima/Excel. In particular, check the white wire be-
Digital sensor reading
tween XnX and Optima/Excel. Note: power must be cycled to reset F153
after correcting the cause.
Input mA
Contact Honeywell Analytics' Service Department.
Indicates that mA input from sensor is less than 3 mA. Check wiring
between XNX and sensor. Also check the switches S3 and S4 are set
Input mA
correctly. If the switch settings need to be change, power down the
transmitter before changing the switch settings. If wiring and switches
are okay, replace sensor.
constant current A/D
Check that correct mV sensor type is selected. Check wiring between
input mV
XNX and sensor. If sensor type and wiring are okay, replace sensor.
Current baseline
Perform zero calibration. If problem persists, replace sensor.
Entire personality
Check that installed option matches the option indicated in the transmit-
part #
ter part number, check wiring to Optima/Excel.
130
Action For Resolution