XNX Universal Transmitter
Applicable
Warning
Description
Sensors
Low Optical
W023
Excel
Sample Signal
Reflex Failure
W024
ECC
Warning
Safety variable
W025
All
fail warning
Warnings/Faults
Frequency of Diag-
Latching / Non-Latching
nostic
XNX polls sensor
every 2 seconds,
Non-latching
diagnostic fre-
quency controlled
by sensor
Dependent on
sensor, typically 8
Latching
hours; Once fault
is detected: every
15 minutes
Latching
2 seconds
Event History Data
Sensor fault or
Check location for external interference or obstructions in the IR path.
warning code
Check sensor for dirty windows. Check Excel alignment. Check Beam
(Note 4)
Block Low Signal Percentage setting in the transmitter.
0
ECC sensor is nearing end of life. Replace sensor.
Note 3
Contact Honeyewell Analytics Service Department.
124
Action For Resolution