XNX Universal Transmitter
Appli-
Fault
Description
cable
Sensors
Sensor Path Ob-
F126
Optima
scured
F127
Beam Block
Excel
Sensor Installation
F128
Excel
Not Complete
Option Communi-
F130
All
cation Failure
F133
Not used
Stabilization
F143
All
Timeout
F145
Reflex Failure
ECC
Unknown Sensor
Optima,
F146
Failure
Excel
Internal option
F148
board hardware
All
failure
Warnings/Faults
Latching / Non-
Frequency of
Latching
Diagnostic
XNX polls sensor
every 2 seconds,
Non-latching
diagnostic fre-
quency controlled
by sensor
XNX polls sensor
every 2 seconds,
Non-latching
diagnostic fre-
quency controlled
by sensor
XNX polls sensor
every 2 seconds,
Non-latching
diagnostic fre-
quency controlled
by sensor
Non-latching
2 seconds
Latching
2 seconds
Dependent on
sensor, typically 8
Non-latching
hours; Once fault
is detected: every
15 minutes
Non-latching
2 seconds
Non-latching
2 seconds
Event History Data
Sensor fault or warn-
Check location for external interference. Check sensor for dirty windows.
ing code (Note 4)
Sensor fault or warn-
Check location for external interference or obstructions in the IR path.
ing code (Note 4)
Check sensor for dirty windows. Check Excel alignment.
Sensor fault or warn-
Check Excel alignment. Perform a zero calibration.
ing code (Note 4)
Option module ID:
Check that installed option matches the option indicated in the transmit-
0=None, 1=Foun-
ter part number. If the option has been changed, the new option must be
dation
Fieldbus,
TM
set up in Information->Transmitter Data as described in the manual.
2=Modbus
, 3=Relay
®
Warm up time (sec-
Cycle power, contact Honeywell Analytics' Service Department if prob-
onds x100)
lem persists.
nA/mV
ECC sensor is no longer functioning properly. Replace sensor.
Sensor fault or warn-
Contact Honeywell Analytics' Service Department.
ing code (Note 4)
Option board error
Contact Honeywell Analytics' Service Department.
status (Note 6)
129
Action For Resolution