Honeywell XNX-AM Series Technical Manual page 50

Hide thumbs Also See for XNX-AM Series:
Table of Contents

Advertisement

XNX Universal Transmitter
MPD CB1, 705 Series.
AWG
Metric Wire Gauge
24
0.25 mm
2
22
20
0.5 mm
2
18
16
1.0 mm
2
* Fluctuations in temperature have a greater impact on smaller wire diameters and therefore may require
more frequent zero calibrations.
5. Wire the pluggable terminal block as shown in the
personality board
illustration then plug the connector into
the back of the mV personality board. In remote mount
MPD configurations, the 3 wires connecting the pluggable
terminal block and the remote MPD must be routed
through the supplied ferrite bead (Honeywell Analytics
part no. 0060-1051, supplied in the accessory kit) as
shown in
Figure
46.
Installation and Operation
Sensepoint Series
MPD IC1, IV1 & IF1 Sensors
Sensors
12m (47 ft.)
30m (97 ft.)
20m (65 ft.)
50m (162 ft.)
30m (97 ft.)
80m (260 ft.)
50m (162 ft.)
120m (390 ft.)*
80m (260 ft.)*
200m (650 ft.)*
Power
Ferrite Bead
for Remote
mV
Sensor Wiring
6. Mount the remote sensor junction box with sufficient room
below to fit the sensor and weatherproof cover.
WARNING
!
Warning: Install the junction box according to local codes and manufacturer's
requirements.
7. Attach the conduit to the remote terminal box. The
junction box provides a mounting base for the sensor and
contains the associated electronic circuit.
8. In the remote junction box, connect the wires from the
transmitter to the 3-way terminal block in the terminal box.
48
Internal Ground Lug
(do not use)
XNX Universal Transmitter
mV
Remote
Sensor
Figure 46. Ferrite bead wiring