Honeywell 2MLF-AV8A User Manual page 37

Analog input module
Table of Contents

Advertisement

Digital output
range
Unsigned value
(-192 ~ 16191)
Signed value
(-8192 ~ 8191)
Precise value
(3808 ~ 20191)
Percentile value
(-120 ~ 10119)
CAUTION
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
September 2010
-0.24
0
-192
0
-8192
-8000
-240
0
-120
0
1.
If analog input value exceeds the maximum range (For example,
20mA), the digital value is fixed at maximum (For example, 16191
for unsigned) as per above table. Likewise, if analog input value
drops below minimum range (For example, 0mA), the digital value
is fixed at minimum (For example, -192 for unsigned) as per above
table.
2.
Voltage and current input should not exceed ±15V and ±30mA,
respectively. Increase in temperature may lead to erratic reading.
3.
You cannot modify the Offset/Gain setting for 2MLF-AV8A/AC8A
module.
Honeywell
2.3. Characteristics of I/O conversion
Analog input current (mA)
5
10
15
4000
8000
12000
-4000
0
4000
5000
10000
15000
2500
5000
7500
2. Specifications
20
20.23
16000
16191
8000
8191
20000
20239
10000
10119
37