7.1
Error codes
Errors which occur when A/D conversion module's RUN LED blinks are as described in
Table 7.
Error Code
(Dec)
10
Module error (ASIC Reset Error).
11
Module error (ASIC RAM or Register Error).
20
Module error (A/D Conversion Error).
30
Module error (EEPROM Error).
Module error (Offset value with the range of 1 ~ 5V or 4 ~ 20mA is
40#
set greater than or equal to Gain value.)
Module error (Offset value with the range of 0 ~ 5V or 0 ~ 20mA is
41#
set greater than or equal to Gain value.)
Module error (Offset value with the range of 0 ~ 10V is set greater
42#
than or equal to Gain value.)
Module error (Offset value with the range of -10 ~ 10V is set greater
43#
than or equal to Gain value.)
50#
Filter constant setting range exceeded.
60#
Time average setting range exceeded.
70#
Count average setting range exceeded.
80#
Analog input range setting error (only for 2MLF-AC8A).
R200
Analog Input Module 2MLF-AV8A, AC8A User's Guide
September 2010
7. Troubleshooting
Table 7 – List of error codes
Description
Honeywell
RUN LED
status
Flickers every
0.2s.
Flickers every
1s.
129