2. Specifications
2.3. Characteristics of I/O conversion
Digital output value for voltage input characteristics is as specified below.
(Resolution (based on 1/16000): 0.3125mV)
Digital output
range
Unsigned value
(-192 ~ 16191)
Signed value
(-8192 ~ 8191)
Precise value
(-60 ~ 5060)
Percentile value
(-120 ~ 10119)
3.
If the range is DC 0 ~ 10V
30
Analog Input Module 2MLF-AV8A, AC8A User's Guide
Analog input voltage (V)
-0.06
0
1.25
-192
0
4000
-
-8192
-4000
8000
-60
0
1250
-120
0
2500
Honeywell
2.5
3.75
5
1200
8000
16000
0
0
4000
8000
2500
3750
5000
5000
7500
10000
September 2010
5.05
16191
8191
5060
10119
R200