UL & NEC/CEC Regulations for the BWX 8305 Basestation
9.
Power-interconnect wires between the power supply/rectifier and the BS unit must have heat shrink
tubing applied over the barrel of the terminal lugs after crimping the wire. A picture is provided in
the "Installation" section of this manual.
10.
External power source / supply considerations for the - 48V and + 24V BS chassis:
a.
b.
c.
d.
AC Power Cord Warning labels for Nordic Countries
Warning
In Finland: " Laite on liitettv suojamaadoituskoskettimilla varustettuun pistorasiaan "
In Norway: " Apparatet má tilkoples jordet stikkontakt "
In Sweden:
BWX 8305 Basestation Installation and Commissioning Guide
1-4
An external method of disconnecting each of the DC power Load/Return lines to the BS chassis
is required, either through fuse+disconnect device(s) or a dual-pole breaker. The fuse/breaker
rating must be minimum 10% higher than that of the BS Chassis breaker but shall not exceed
70A.
The external DC power source, if current limited, shall have the limit set-point configured
higher than the BS Chassis breaker rating.
The external supply "Return" and the BS chassis shall be bonded to a common Earth ground.
The BS Chassis has an external ground lug provided.
Do not remove protective earth connection before disconnecting the BS from the DC power
supply.
" Apparaten skall anslutas till jordat uttag "
Chapter 1
Safety
OL-16336-02