Chapter 6. COMMREQ/Data_Init_Comm Programming
Read Identification Reply Data
The datagram returned by the target Genius Device has the following data content:
Word #
MSB
0
Output data length (bytes)
1
Number of diagnostic data bytes
2
Device Status Table Address (LSB)
Device Model Number OR
3
GENA application ID if a GENA
Assigned controller bus address
4
OR S6 GBC DIP switch, if S6 GBC
OR GENA application rev #, if GENA
Baud Rate Code
Bits
0 0 0 0 x x x x 153.6 K baud, extended
5
0 0 0 1 x x x x 153.6 K baud, standard
0 0 1 0 x x x x 76.8 K baud
0 0 1 1 x x x x 38.4 K baud
74
Baud Rate
PACSystems RX3i Genius Communications Gateway
Description
LSB
Input data length (bytes)
Number of configuration data bytes
Device Status Bits
Bit
Description
0
Device Forced if set to 1
1,2
01 = inputs only
10 = outputs only
11 = combination
3
HHM Present if set to 1
4
BSM Present if set to 1
5
BSM Controller if set to 1
6
BSM Actual State
7
BSM Forced if set to 1
Device Status Table Address (MSB)
Device Software Revision Number
Device Model Number