Chapter 6. COMMREQ/Data_Init_Comm Programming

COMMREQ #5: Clear Circuit Fault Command

This command is used to clear any faults on a specified circuit of a targeted Genius I/O device.
Command Block for the Clear Circuit Fault Command
Address
Command Length
Address +1
No Wait
Address +2
Status Block memory type
Address +3
Status Block offset
Address +4
Idle timeout value
Address +5
Max. communications time
Address +6
Command number
Address +7
PROFINET Device number
Address +8
Genius Device Number
Address +9
Relative Circuit Number
66
4
0
70 (%I), 72 (%Q), 8 (%R), 10 (%AI), 12 (%AQ) or 196 (%W)
Beginning address for the COMMREQ Status Block.
0
0
5
1-255: The device number of the targeted GCG Genius Gateway.
1-29: the SBA of the targeted Genius Device.
This is the relative number of the circuit within the Genius device. It is
not its reference number assigned in CPU Memory. The first circuit on the
Genius device is considered to be number 1.
For example, to clear faults on discrete I/O block circuit #5, enter 5 here.
For a 4-Input/2-Output analog block, circuit numbers 1 to 4 are for input
channels, 5 and 6 are for output channels.
PACSystems RX3i Genius Communications Gateway
GFK-2892F