6.3 COMMREQ Command Block Format

The first step in programming communications requests is to set up the contents of the COMMREQ instruction.
This can be done using Block Moves or similar program instructions, as shown later in this chapter.
CPU Memory
Command Block
Data is placed in adjacent locations in CPU memory to form a Command Block, per the format shown below:
The length of the Command Block depends on the type of COMMREQ being sent. Seventy words is the
maximum and is used only for a COMMREQ that transfers a 128–byte datagram. Most Command Blocks are
much shorter. The table in Section 6.3.3 gives an overview of the contents of each type of COMMREQ that may
be sent to a PROFINET Controller for transfer to a Genius Gateway.
GFK-2892F
Location
Data Field
address
Data Block Length
address + 1
Wait/No Wait Flag
address + 2
Status Pointer Memory Type
address + 3
Status Pointer Offset
address + 4
Idle Timeout Value (ms)
address + 5
Max. Communication Time (ms)
address + 6 to
Data Block
address + 78
March 2019
Chapter 6. COMMREQ/Data_Init_Comm Programming
Application Program
Edit content of COMMREQ
Value
Always 0
Always 0
Always 0
51