COMMREQ #8: Enable/Disable Outputs Command

The Enable/Disable Outputs command can be sent to the Genius Gateway to disable sending outputs to any
blocks whose outputs are currently enabled. Conversely, it can also be used to enable sending outputs to any
blocks whose outputs are currently disabled. The effect of disabling outputs is the same as running the control
in Run/Disable mode.
Command Block for the Enable/Disable Outputs Command
Address
Command Length
Address +1
No Wait
Address +2
Status Block memory type
Address +3
Status Block offset
Address +4
Idle timeout value
Address +5
Max. communications time
Address +6
Command number
Address +7
PROFINET Device number
Address +8
Genius Device Number
Address +9
Enable/Disable Command
GFK-2892F
Chapter 6. COMMREQ/Data_Init_Comm Programming
4
0
70 (%I), 72 (%Q), 8 (%R), 10 (%AI), 12 (%AQ) or 196 (%W)
Beginning address for the COMMREQ Status Block.
0
0
8
1-255: The device number of the targeted GCG Genius Gateway.
Enter 1-29 to enable or disable outputs to one block. Or
enter 255 to enable or disable outputs to ALL devices on the bus.
To disable outputs, enter 0. To enable outputs, enter 1.